Introduction
F8 ultrasonic flowmete adopts advanced modular all-in one design, independent menu operation, LCD backlight display, WlFl communication, it is suitable for the continuous measurement of building automation system, meeting different measurement requirements. The unique digital signal processing technology enhances the anti-interference ability. Combined with the precision clamp on or insertion flow sensor, more accurate measurement, simpler installation way, easier maintenance mode.
Advantages
Product Characteristics:The application range of the meter is very wide. After being installed,the meter can directly measure water flow (air-conditioning cooling can be measured).
Gentos icloud system service:WiFi connected icloud service.Users can inquire data on mobile terminalin or PC web realtime and know each information at anytime.Users can upgrade application by remote control.
Energy efficiency monitoring:The meter has energy efficiency monitoring system.The measured datainformation can be monitored in real time and data curve can be observedin real time,generating data report.
Built in SD card data storage function:The meter has a built-in 8G big capacity SD card, with strong data acquisition and storage function. lt collects the flow, flow rate, net accumulation, positive accumulation and negative accumulation corresponding to each time to ensure no data loss.
Easy installation:The meter supports wall mount installation and clamp on pipe installation. The clamp on pipe installation installs meter transmitter on measured pipe line, thus reducing the trouble of cable routing, which will save so much time and energy. And then the meter coordinates icloud service,every data will be great clear.
Performance Index | |
Flow range | ±(0.03ft/s ~ 40 ft/s) ±(0.01m/s ~ 12 m/s ) |
Accuracy | ± 0.5% of measured value |
Repeatability | 0.15% |
Linearity | ±0.5% |
Functional Index | |
Output
| Analog output: 0/4 ~ 20 mA, ( max load 750 Ω ); Pulse output: 0 ~ 9999 Hz, OCT ( min. and max. frequency is adjustable ); Relay output: max. frequency 1Hz ( 1A@125VAC or 2A@30VDC ). |
Communication Interface | RS232 & RS485 |
Power Supply | 90 ~ 245 VAC (48 ~ 63 Hz) Or 10 ~ 36 VDC |
Keypad | 22 light tactile keys |
SD Card ( standard ) | Max record: 512 days Record time interval: 1 ~ 3600 s |
WIFI | Frequency range: 2.412~2.484GHz |
Transmitting power: 802.11b 16±2 dBm 802.11n 13±2 dBm 802.11g 14±2 dBm | |
Working temperature:-20~85℃ | |
40m transmission distance in open environment40 | |
Display | 20 × 2 lattice alphanumeric, backlit LCD |
Temperature | Transmitter: 14℉ to 122℉ ( -10℃ ~ 50℃ ) Transducer: -40 °F ~ 176 °F ( - 40 ℃ ~ 80 ℃, standard ) |
Physical Characteristics | |
Transmitter | NEMA13 ( IP54 ). |
Transducer | Encapsulated design, IP68; Standard cable length: 5m. |
Weight | Transmitter: approximately 1.0kg. |
Wiring Diagram
Water supply, Water treatment, Irrigation, Boiler, Power plant, HAVC chilled water, inland aquaculture water, etc.
Certificate
Detectable Fluids
Compatible Pipe Materials